COMMERCE BUSINESS DAILY ISSUE OF APRIL 3,2000 PSA#2570Department of the Air Force, Air Education and Training Command,
Goodfellow AFB, Contracting Squadron, 210 Scherz Blvd, Bldg 707,
Goodfellow AFB, TX, 76908-4705 41 -- CHILLER SOL F41614-00-T0024 DUE 041400 POC Charles Frerich,
Contract Administrator, Phone 915-654-4423, Fax 915-654-4427, Email
charles.frerich@goodfellow.af.mil -- Mike Cook, Chief, Base Operations
Flight, Phone 915-654-5164, Fax 915-654-4427, Email WEB: Visit this
URL for the latest information about this,
http://www.eps.gov/cgi-bin/WebObjects/EPS?ACode=P&ProjID=F41614-00-T00
24&LocID=584. E-MAIL: Charles Frerich,
charles.frerich@goodfellow.af.mil. This is a combined
synopsis/solicitation for commercial items prepared in accordance with
FAR subpart 12.6, as supplemented with additional information included
in this notice. This announcement constitutes the only solicitation,
proposals are being requested and a written solicitation will not be
issued. The solicitation number is F41614-00-T0024 and is issued as a
request for quotation. Responses/Offers are due by 4:00 PM CST, --
April 14, 2000. Please visit www.eps.gov and register to automatically
receive procurement notifications from EPS. The system will inform
you, via e-mail, when there has been activity on EPS concerning this
solicitation. Solicitation provisions are those in effect through
Federal Acquisition Circular 97-15 and DCN 20000210. The government
desires delivery within 30 days of receipt of order. FOB point:
Goodfellow AFB, TX 76908. Chiller, 60 ton, air cooled, 230V 3 phase,
R-22 refrigerant, semi-hermitic scroll type compressor (3600 RPM)
cooling capacity: 52.7 tons, evaporator water flow: 127 gpm @ 44
degrees, fouling factor .00025. Unit shall include manufacturer's
descriptive literature, start-up instructions, and maintenance
procedures. Unit shall include following failure protections: loss of
chilled solution flow, chiller freeze protection, chilled solution flow
interlock, head pressure control, pump down control, low ambient start,
hot start control and low ambient lockout. Unit shall include the
following controls: auto/stop switch, leaving water temperature
setpoint adjustment and a Delta T adjustment (viewable through the unit
Human Interface digital display). Display shall include the following
failure controls: loss of chilled water flow, high/low refrigerant
pressure switch(s), oil pressure switch, loss of refrigerant charge,
high motor winding temperature, and low temperature thermostat
operation. Unit shall include the following operating controls: leaving
chilled water temperature control, timer (prevents compressor from
short cycling), periodic pump down, load limit thermostat, low ambient
control (consisting of external damper assembly that controls head
pressure for operation down to 0 degrees F, 10 degrees F with hot gas
bypass), hot gas bypass (sized for minimum compressor loading), and
chilled water set point. Unit shall include lead-lag function that
either by mechanical or microprocessor devices alternates the usage of
compressors. Unit shall include an electronic device that monitors
each refrigeration circuits suction, liquid and discharge temperatures
and pressures, calculates superheat and subcooling temperatures and
displays on unit Human Interface. Unit shall include for each
refrigerant circuit: liquid line solenoid valve, filter dryer, liquid
line sight glass and moisture indicator, thermal expansion valve,
charging valve, liquid line shut-off valve, compressor discharge
service valve. Unit must conform to standards ANSI /AR 590 and
ANSI/ASHRAE standard 15-1994. MFR: Trane MN: CGAFC604, or equal. State
warranty provisions in offer. Solicitation Provisions Incorporated by
Reference (Feb 1998): This solicitation incorporates one or more
solicitation provisions by reference, with the same force and effect as
if they were given in full text. Upon request, the Contracting Officer
will make their full text available. The offeror is cautioned that the
listed provisions may include blocks that must be completed by the
offeror and submitted with its quotation or offer. In lieu of
submitting the full text of those provisions, the offeror may identify
the provision by paragraph identifier and provide the appropriate
information with its quotation or offer. Also, the full text of a
solicitation provision may be accessed electronically at this/these
address(es): farsite.hill.af.mil. The following solicitation provisions
are incorporated by reference: FAR 52.212-1, Instructions to Offerors,
Commercial Items; FAR 52.212-2, Evaluation Commercial Items, with the
following amendment: "The following factors shall be used to evaluate
offers: Price, past performance, and delivery schedule;" FAR 52.212-3,
Offeror Representations and Certifications, Commercial Items. The
following clauses apply to this acquisition: FAR 52.212-4, Terms and
Conditions, Commercial Items; FAR 52.212-5, Contract Terms and
Conditions Required to Implement Statutes or Executive Orders --
Commercial Items. FAR 52.212-5 has the following blocks checks:,
Affirmative Action for Disabled Veterans and Veterans of the Vietnam
Era; FAR 52.222-36, Affirmative Action for Workers with Disabilities;
FAR 52.222-37, Employment Reports on Disabled Veterans and Veterans of
the Vietnam Era; FAR 52.225-3, Buy American Act, Supplies; and, FAR
52.232-22, Payment by Electronic Funds Transfer -- Central Contractor
Registration. Offerors must send a completed copy of FAR 52.212-3,
Offeror Representations and Certifications, Commercial Items, with
offer. POC: SSgt Patrick Foster, patrick.foster@goodfellow.af.mil,
phone (915) 654-5164 Contracting Officer: Mike Cook,
mike.cook@goodfellow.af.mil, phone number (915) 654-5134, fax number:
(915) 654-4427. Mailing Address: 17 CONS/LGCB, 210 Scherz Boulevard,
Goodfellow AFB, TX, 76908. Posted 03/30/00 (D-SN439625). (0090) Loren Data Corp. http://www.ld.com (SYN# 0236 20000403\41-0001.SOL)
41 - Refrigeration, Air Condition and Air Circulating Equipment Index Page
|
|