COMMERCE BUSINESS DAILY ISSUE OF APRIL 21,2000 PSA#2584Department of Transportation, Maritime Administration (MARAD), South
Atlantic Region, 7737 Hampton Blvd., Bldg. 4D Rm-211, Norfolk, VA,
23505 61 -- 250 MCM, 1 KVA SUBMERSIBLE POWER CABLE SOL DTMA2Q00029 DUE
051100 POC Milton Spears, Contracting Officer, Phone (757) 441-3245,
Fax (757) 441-6080, Email glen.spears@marad.dot.gov -- Toni Kimbrough,
Contracting Officer, Phone (757) 441-3246, Fax (757) 441-6080, Email
WEB: Visit this URL for the latest information about this,
http://www.eps.gov/cgi-bin/WebObjects/EPS?ACode=P&ProjID=DTMA2Q000
29&LocID=801. E-MAIL: Milton Spears, glen.spears@marad.dot.gov.
This is a combined synopsis/solicitation for commercial items prepared
in accordance with the format in Subpart 12.6, as supplemented with
additional information included in this notice. This announcement
constitutes the only solicitation; proposals are being requested and a
written solicitation will not be issued. Description of requirement:
three conductor, 250 MCM submersible cable (ground conductor is
optional) having a minimum insulation rating of 1 KVA; cable to be
delivered on non-returnable reels in lengths of not more than 1,000
feet nor less than 500 feet; conductors shall be bunched strands of
coated copper dead soft per ASTM B3 consisting of not less than 300
strands per conductor; insulation shall be ethylene propylene rubber
(EPR) meeting ASTM D-2802 or equal; insulation on each conductor shall
be marked or color-coded to identify each separate conductor the
entire length of the cable; insulation shall be rated heat resisting to
90 degrees C; cable shall have suitable fillers to provide for high
impact resistance and high flexibility; cable shall be jacketed with 90
degree C rated neoprene or equal; jacket shall have minimum thickness
of 0.245 inches which exceeds requirement of ASTM D-4247 and have
double belted construction; jacket shall provide protection from
abrasion, impact, heat, oil, ozone, flame, alkali, acids and water
penetration; jacket shall, at set intervals, have identifying data
which is branded into jacket with indented or embossed letters that are
highly resistant to scuffing; ampacity rating of cable shall be a
minimum 320 amps 660 VAC continuous duty at 90 degrees C copper
temperature when operating at 40 degrees C in open air; cable must be
suitable for submersible application for normal expected life of the
product; vendor to provide manufacturer's standard commercial limited
warranty guaranteeing the cable to be free of defects in material and
workmanship valid for a period of not less than one year. Quantity
required: 5,000 feet. The cost of freight is to be included in the
price of the cable. The cable is to be delivered within 120 calendar
days following receipt of order FOB at James River Reserve Fleet, End
of Harrison Road, Building 2606, Ft. Eustis, VA 23604. Posted 04/19/00
(D-SN446696). (0110) Loren Data Corp. http://www.ld.com (SYN# 0278 20000421\61-0005.SOL)