COMMERCE BUSINESS DAILY ISSUE OF JULY 7,2000 PSA#2637MEDCOM Contracting Center, Attn: MCAA-C, 2107 17th Street, Building
4197, Fort Sam Houston, TX 78234-5015 S -- PRIVATIZATION OF ELECTRIC DISTRIBUTION AND METERING SYSTEM
UTILITIES AT FORT SAM HOUSTON AND CAMP BULLIS TX SOL DADA10-99-R-0016
DUE 100300 POC Contract Specialist Robert Barnea, (210) 221-5773;
Contracting Officer Maria M. Moncada WEB: Site is in developement, send
e-mail for solicitation., hcaa.medcom.amedd.army.mil. E-MAIL: Site is
in developement, send e-mail or call.,
robert.barnea@cen.amedd.army.mil. RE: A-082 DESC: The U. S. Army seeks
to privatize, pursuant to 10 U.S.C. 2688, electricity distribution and
metering systems at Fort Sam Houston, and Camp Bullis, Texas. The U. S.
Army intends to transfer ownership and access easements for the
electric utility distribution and metering systems to an electric
utility service provider able to provide reliable utility service for
an indefinite and ongoing period, while complying with all federal,
state and local laws, rules and regulations. The transferee/buyer will
be obligated to provide electric distribution and metering service for
Fort Sam Houston and Camp Bullis. The electric distribution system to
be conveyed includes all components between the power provider
substation meters and the electric disconnect at each facility service
point. Fort Sam Houston's electrical distribution system consists of
a two-section metal clad outdoor switch gear, Westinghouse Model
PH-54443-Y1 VAC-CLAD Type VCP-W. Each section is served by a 2000 Amp
underground feeder consisting of four per phase, 750MCM, 15kv copper
shielded cables. One section contains three distribution feeder
breakers and one space. The second section contains six distribution
feeder breakers. All feeders exit the switch station under ground to
riser poles located across the street, except for one underground
express feeder to the Brooke Army Mecical Center (BAMC) Hospital. The
distribution system at Fort Sam Houston consists of ten, three phase
heavy feeders approximately 60 miles in length, and approximately 60
miles of three phase equivalent laterals. All feeders are rated 480
amps at 13,200 volts. The feeders are looped and cross tied at various
points using either gang operated air break pole mounted switches or
R-VAC pad mounted vacuum under oil switches. There are approximately
1200 distribution transformers serving 1332 buildings at nominal user
voltages. Camp Bullis is served by one General Electric metal clad
outdoor switch gear with one feeder breaker and one spare breaker rated
480 amps at 13,200 volts. The distribution system consists of a three
phase feeder serving approximately 245 buildings with approximately 30
miles of three phase equivalent circuits with approximately 150
transformers. Installation street lighting has been excluded. Amendment
03 has been issued establishing October 3, 2000 for receipt of offers.
PROCEDURES: THIS A COMPETITIVE REQUEST FOR PROPOSALS. Small Business
interests shall note the FAR Part 19 Standard Industrial Codes (SIC)
and Size Standards (SS) for the electric utility systems identified in
this announcement. The following apply. SIC/SS: 4911/4 Million (M)
Megawatt hours, or 4931/$5M. REQUESTED RESPONSE: Interested parties
should provide a statement of interest on company letterhead. Elaborate
proposals or pricing information is neither required nor desired. Under
no circumstances will cost data for the existing systems be provided.
Fort Sam Houston and Camp Bullis are normally open to the public. Call
for access to the document room or for site orientation. Itshould be
noted that the RFIs and solicitations for utility systems at different
Defense Installations may be issued during the same time frame. A
separate response to each RFI or solicitation is required. e-mail:
robert.barnea@cen.amedd.army.mil, or by facsimile at (210) 221-4123, or
telephone at (210) 221-5773. You may also send written responses to our
POC: MEDCOM Contracting Center, Attn: Robert Barnea, 2107 17th St.,
Fort Sam Houston, TX 78234-5015. Proposals are due no later than
October 3, 2000. Posted 07/05/00 (W-SN471496). (0187) Loren Data Corp. http://www.ld.com (SYN# 0049 20000707\S-0004.SOL)
S - Utilities and Housekeeping Services Index Page
|
|