Virginia Beach, VA 23460-5120 41 -- AIR COOLED ROTARY CHILLER TRANE MODEL #RTAA-125 OR APPROVED
EQUAL SOL N60191-00-Q-0005 DUE 082500 POC Lou Hemmings 757-433-3442
E-MAIL: Lou E Hemmings, 757-433-3442 fax 2176,
hemmingsl@nasoceana.navy.mil. RSO Oceana in Virginia Beach, VA is
issuing Solicitation # N60191-99-Q-0005 as a request for quote (RFQ)
for One Packaged Air Cooled Rotary Chiller, Trane Model #RTAA-125 or
approved equal with the following minimum features and accessories:
1)Nominal 125 tons cooling. 2)460/3/60 input power. 3)Single 115/1/160,
15 amp connection F evaporator barrel heater tape and control power.
4)Provide a factory mounted and wired control power transformer 5)Dual
independent refrigerant circuits. 6)Compressors shall be rotary
(screw) type. (reciprocating compressors ARE NOT acceptable. 7)Provide
modulated unloading of 15 percent capacity (provide factory install
hot gas bypass on both refrigerant circuits if chiller cannot unload to
15 percent). 8)Factory installed low ambient head pressure controls for
cooling to 25 degrees fahrenheit. 9)Refrigerant suction and discharge
pressure display for each refrigerant circuit. 10)over/under voltage
protection, factory mounted and wired. 11)Phase failure/reversal
protection, factory mounted and wired. 11)Phase failure/reversal
protection, factory mounted and wired. 12)Louvered condenser hail
guards with maximum openings of 1 half inch x 6 inch (must completely
cover condenser coils and compressor/evaporator access area). Wire
screens are not accptable equal. 13)Factory charges with refrigerant
and oil. 14)Factory mounted and wired compressor starts counter and run
time meter for each compressor. 15)Microprocessor control of leaving
water temperature with digital display of entering and leaving water
temperatures, operating mode and diagnostic service information.
Microprocessor must be capable of accepting either A 0-10 Vdc or 4-20
mA chilled water reset signal. 16)Vaporproof water flow switch provided
for field mounting and wiring. 17)Provide the services of the
manufactures service company for start-up, checkout and 12 months
parts, refrigerant and labor warranty. REQUIRED PERFORMANCE DATA:
Minimum Cooling Tons 122.5 EWT 52.8 Degrees Fahrenheit LWT 45.0 Degrees
Fahrenheit GPM 375 Maximum WPD 33 Feet Design Ambient 92.0 Degrees
Fahrenheit Low Ambient 15.0 Degrees Fahrenheit Minimum Full Load
Efficiency 10.2 EER Minimum Part Load Efficiency 12.9 NPLV Modulated
Unloading 15 Percent -- 100 Percent Volts/Phase/Hz 460/3/60 MCA 253
AMPS MFS 350 AMPS ALL PERFORMANCE DATA SUBMITTED MUST BE RATED AND
CERTIFIED IN ACCORDANCE WITH ARI STANDARD 590-98 This announcement
constitutes the only solicitation; proposals are being requested and a
written solicitation will not be issued. The solicitation document and
incorporated provisions and clauses are those in effect through Federal
Acquisition Circular 97-18. The provisions at 52.212-1, Instructions to
Offerors -- Commercial; 52.212-2, Evaluation -- Commercial Items;
52.212-3, Offeror Representations and Certifications -- Commercial
Items; 52.212-4, Contract Terms and Conditions -- Commercial Items; and
252.204-7004, Required Central Contractor Registration apply. Posted
08/09/00 (W-SN484094). (0222) Loren Data Corp. http://www.ld.com (SYN# 0216 20000811\41-0001.SOL)