COMMERCE BUSINESS DAILY ISSUE OF AUGUST 16,2000 PSA#2665 U.S. Department of Interior, Bureau of Indian Affairs, San Carlos
Irrigation Project, P.O. Box 250, Coolidge, AZ 85228 61 -- PAD MOUNT TRANSFORMERS SOL 0H59SCIP007 DUE 090100 POC Mary Lou
Tiznado, (520) 723-6210 E-MAIL: MaryLTiznado@bia.gov,
MaryLTiznado@bia.gov. The Bureau of Indian Affairs, San Carlos
Irrigation Project is soliciting quotations for the purchase of three
(3) pad mount transformers. San Carlos Irrigation Project is located at
13805 North Arizona Boulevard, Coolidge, Arizona 85228. Coolidge is
located in Pinal County in central Arizona. The transformers are to be
2,500 KVA, 3-phase, pad mount, 12,470 volts and delta wound primary,
480Y/277 Y-connected, grounded secondary. Copper or aluminum windings
on both or either high and low voltage windings, primary taps 2.5%
above and below nominal, dead front wells and inserts, bayonet fusing,
spade connector, pressure relief. Transformer shall comply with all
ANSI, IEEE, NEMA and REA Standards, Guides and Bulletins as explained
in the specifications below. In addition, quote should provide
information on the type of winding (copper or aluminum) to be used on
both windings. PAD MOUNTED DISTRIBUTION TRANSFORMER SPECIFICATIONS SAN
CARLOS IRRIGATION PROJECT (SCIP) SPECIFICATIONS & REQUIREMENTS The
transformer(s) shall comply with the most recent publication of the
following specifications: -- Rural Electrification Administration (REA)
Specifications for Pad-Mounted Transformers, single and three phase,
Bulletin 50-73. -- ANSI/IEEE General Requirements for Liquid-Immersed
Distribution, Power and Regulating Transformers, C57.12.00-1993. --
IEEE Requirements for Pad-Mounted, Compartmental-Type Self-Cooled,
Single Phase Distribution Transformers with Separable Insulated
High-Voltage Connections; High-Voltage 34,500 Grnd. Y/19,920 volts and
below; Low-Voltage, 240/120 volts, 2500 KVA and small, C57.12.26-1990.
-- ANSI/IEEE Terminal Markings and Connections for Distribution and
Power Transformers. C57.12.70-1978. -- IEEE Terminology for Power and
Distribution Transformers, C57.12.80-1978. (Reaff., 1992, ANSI). --
ANSI/IEEE Test Code for Liquid-Immersed Distribution Power, and
Regulating Transformers and Guide for Short-Circuit testing of
Distribution and Power Transformers, Part I and Part II,
C57.12.90-1987. -- ANSI/IEEE Guide for Loading Mineral-Oil Immersed
Overhead and Pad-Mounted Distribution Transformers Rated 500 KVA and
less with 65 degree C average winding rise, C57.91-1995. -- NEMA TR-1
Transformers, Regulators and Reactors. The pad-mounted transformers
shall be of dead front design with all access doors secured by a
recessed, captive, pentahead bolt and have NEMA safety label per NEMA
Publication 260-1982. In addition, the transformer(s) shall be of a
manufacture and type included in the most recent REA Bulletin 43-5,
"List of Materials Acceptable for use on systems of REA Electrification
Borrowers". The requested transformer(s) is for the quantity, voltage
rating, KVA rating, type and have the accessories indicated in the
following tabulation: ITEM: 1 QUANTITY NUMBER: 3 PRIMARY VOLTAGE --
CAPITAL LETTER: A SECONDARY VOLTAGE -- SMALL LETTER: b KVA RATING
NUMBER: 2,500 ACCESSORIES AND TYPE -- APPLICABLE NUMBERS: 1, 3, 5, 7 &
8 PRIMARY VOLTAGE: A. 12,470 volts, delta wound. SECONDARY VOLTAGE: a.
120/240 volts. b. 480Y/277 volts, grounded Y wound. ACCESSORIES, TYPE
AND SPECIAL REQUIREMENTS: 1. Internal bayonet fuses. 2. Two high
voltage load break bushing wells. 3. Single high voltage load break
bushing wells for radial feed with inserts. 4. Direct connected MOV
arrester. 5. Two 2-1/2% primary taps above and below rated voltage. 6.
Secondary thermal overload breaker. 7. Interlaced secondary windings.
8. Three (3) low voltage bushings with paddles. The successful
supplier shall provide free of charge a certified test report to SCIP
detailing the no-load and load-losses of all transformers as tested in
accordance with C57.12.90-1993 Section 8 (no load losses) and Section
9 (load losses). If the average no-load or load losses exceed the
guaranteed values, SCIP may either reject the batch of transformers or
reduce the purchase price by 1.25 times the above quoted respective
loss values. The transformer(s) shall have mineral oil insulation with
less than two (2) parts per million polychlorinated biphenyl (PCB). TO
BE COMPLETED BY BIDDER: GUARANTEED / LOSSES ITEM QUANTITY UNIT DELIVERY
IN NO-LOAD LOSSES LOAD LOSSES PRICE WEEKS, ARO IN WATTS IN WATTS ____
_________ _____ ___________ ______________ ___________ Partial
shipments are acceptable. Please give estimated ship date(s).
INTERESTED PARTIES MUST RESPOND WITH THEIR QUOTATIONS, NO HARD COPIES
OF THIS RFQ WILL BE MAILED/FAXED. TO SUBMIT BY E-MAIL, THE ADDRESS IS:
MaryLTiznado@bia.gov THE FAX NUMBER IS (520) 723-9044. THE MAILING
ADDRESS IS: USBIA, SAN CARLOS IRRIGATION PROJECT, P. O. BOX 250,
COOLIDGE, AZ 85228. All quotations must be received by 2:30 P.M.
(MOUNTAIN STANDARD TIME) on 09/01/00. Posted 08/14/00 (W-SN485560).
(0227) Loren Data Corp. http://www.ld.com (SYN# 0275 20000816\61-0006.SOL)