COMMERCE BUSINESS DAILY ISSUE OF AUGUST 23,2000 PSA#2670 Fleet and Industrial Supply Center, Contracting Department, PO Box 97,
Jacksonville, Florida 32212-0097 56 -- CONCRETE DOCKING BLOCKS SOL N46450-00-T-0053 DUE 090500 POC
Donna M Hill 912-673-2656 E-MAIL: Click here to contact the contracting
officer via, DONNA_M_HILL@JAX.FISC.NAVY.MIL. Docking Blocks -- "A" and
"B" Quantity of 15 each of "A" and 15 each of "B" Concrete
construction shall conform to the requirements of ACI 301 AND ACI 318.
Concrete shall be air-entrained having a minimum ultimate compressive
strength of 3,000 psi at 28 days. Cement shall conform to ASTM C150,
TYPE II OR TYPE III. If TYPE III is used, Tri-Calcium Aluminate shall
be 8% or less of the mixture and compressive strength at 7 days must
exceed 3,000 psi. Aggregate shall conform to ASTM C33 with 1 1/2"
maximum size. Reinforcing steel shall conform to A615-Grade 60. Pipe
shall conform to ASTM A53 and shall be hot-dip galvanized, any
available type and grade, 1" NPS Schedule 40. (Drawing available upon
request) Posted 08/21/00 (W-SN488429). (0234) Loren Data Corp. http://www.ld.com (SYN# 0214 20000823\56-0001.SOL)