CONSTITUTES AMENDMENT NO. 1 TO THE COMBINED SYNOPSIS/RFQ FOR a 200 KW
EMERGENCY ENGINE GENERATOR SET. Companies shall acknowledge all
amendment(s)in their quote. This notice serves as the official
amendment to subject synopsis/RFQ and a written amendment will not be
issued. The purpose of this amendment is to respond to the following
questions which were submitted. 1) Will the generator be installed
inside or outdoors? Answer: The generator will be outside. 2) If
outdoors does the enclosure need sound attenuation? Answer: The outdoor
enclosure does not need sound attenuation. The only sound attenuation
is on the exhaust. 3) Is an automatic transfer switch required? Answer:
Yes. An automatic transfer switch is required (400 amp. 3 pole, 4 wire,
Automatic Transfer Switch in a NEMA 1 enclosure with engine start
contacts, shipped loose for field mounting). 4) What is the approximate
distance from the generator location and the power panel being
supplied? Answer: The approximate distance is 90 feet. 5) Is the unit
enclosed in a weather proof enclosure? Answer: Yes, the unit will need
a weather proof enclosure as it will be installed outside. 6) Main
Line Circuit Breaker Required? Answer: Yes, a main line circuit breaker
is required. The circuit breaker in section 4.4 of the specifications
was intended to be a main line circuit breaker. 7) What type of fuel
tank is required, if any, what capacity? Answer: The fuel tank
described in section 3.6 was intended to be mounted with the generator
on the same size pad. The capacity was stated to hold enough fuel to
last 24 hours, assuming 100% loaded. 8) What grade silencer? Answer:
The exhaust silencer was described as an industrial rated exhaust
silencer that will attenuate the exhaust noise to less than 75 dBA at
3 feet. The due date for receipt of offers is not extended. Documents
related to this procurement are available over the Internet and are in
Microsoft Office Suite (Word 6.0, Excel 5.0, or PowerPoint 4.0) format
and reside on the World Wide Web (WWW) server which may be accessed
using a WWW browser application. The Internet site, or URL, for the
NASA/JSC Business Opportunities home page is