COMMERCE BUSINESS DAILY ISSUE OF SEPTEMBER 8, 2000 PSA #2681
SOLICITATIONS
61 -- GENERATOR
- Notice Date
- September 6, 2000
- Contracting Office
- Department of the Air Force, Air Combat Command, 355 CONS, 3180 S Craycroft Rd, Davis Monthan AFB, AZ, 85707-3522
- ZIP Code
- 85707-3522
- Solicitation Number
- F02601-00-Q-0127-A
- Response Due
- September 8, 2000
- Point of Contact
- Douglas Crowley, Contract Specialist, Phone 520-228-2217, Fax 520-228-5284, Email douglas.crowley@dm.af.mil -- Carlos Acosta, Contract Specialist, Phone 520-228-3873, Fax 520-228-5284, Email
- E-Mail Address
- Douglas Crowley (douglas.crowley@dm.af.mil)
- Description
- Provide following requirement: Electric generator, synchronous rated at 156.5 KVA, .8 power factor, 125 KW, 277/480 V., 3 phase, 60 Hz, 1800RPM, 12 wire reconnectable with 2% voltage regulation and adjustable plus or minus 10%. Voltages available include 120 V/208 V, 277/480 wye or 115 V delta and 230 V delta. Motor: Induction, 200 HP, 1500 RPM, 380 V, 3 phase, 50 Hz input with a reduced voltage motor starter and on-off pushbuttons with motor on light mounted in the control panel. Control panel: Nema 12, unit mounted inside weatherized enclosure, containing an across the line motor starter assembly, on-off pushbuttons, motor on light, voltage adjust potentionmenter, output circuit breaker, voltmeter, ammeter, frequency meter, phase selector switch all 3 12_ square, with current transformers and control wiring coded and marked to terminal blocks. Two control manuals are included. Drive: The drive will be a vee belt type with the motor and generator mounted on a horizontal welded steel base with belt tension adjustment. Frequency output 60 Hz + .5/-.3 Hz with 50 +/- 0 Hz input. Enclosure: The unit will be enclosed in a weatherproof ventilated, enamelled-aluminunized steel enclosure with forklift slots in the base for handling. Additional items to be included in the quote are a) disconnect switch 1ea b) 600 MCM Input Cable 200ft c) 3/0 Output Cable Shipping: Calculate shipping to the following address: 49 MMS/BME 1273 Bear Path Rd Holloman AFB, NM 88330-7901 Attn: Mr. Coward or SSgt Izzard Telephone: 505-572-7471 or 7472
- Web Link
- Visit this URL for the latest information about this (http://www2.eps.gov/cgi-bin/WebObjects/EPS?ACode=P&ProjID=F02601-00-Q-0127-A&LocID=882)
- Record
- Loren Data Corp. 20000908/61SOL002.HTM (D-250 SN493467)
| 61 - Electric Wire and Power and Distribution Equipment Index
|