BLDG 1950, FORT SILL OK 73503-0189 Z -- HVAC RENOVATION, USARC FINKBEINER, LITTLE ROCK, AR. SOL
DABT39-95-B-0038 DUE 080795 POC Contract Specialist Dewayne Cochrane
(405) 442-4315 (Site Code W804A6) Principal features of this project
are as follows: Furnish all required plant, labor, equipment, and
materials to complete all work in accordance with the drawings and
specifications for the following: Remove the two steam boilers from the
existing boiler room, and the existing controls system. Remove the
existing 18 through the wall A/C units, and the existing heating steam
fin tube radiators, and the existing steam piping except where it can
be reused. Remove the four existing steam heating and ventilation
units suspended from the ceiling of the assembly room. Remove the steam
heating ventilation air handler serving the basement storage area.
Remove all steam traps and accessories, and steam condensate return
pumps, and circuits for 18 thru-wall A/C units. Remove circuits for
four ceiling hung fan and coils, and circuit for steam condensate
return pumps. Install new heating and cooling fan coil units in areas
now served by through wall units and two additional locations in the
basement. Install new cabinet heating convectors at the entry to
replace the existing, and new hot water fin tubes to replace existing
units in the toilets. Eliminate heating unit from the ceiling of the
shower room. Patch wall openings where through the wall units have been
removed. Install a new air cooled chiller to serve the fan coil units,
and install new chilled water piping from the chiller to the boiler
room. Install new 2-pipe heating/cooling piping from the boiler room to
all of the equipment. Reuse steam piping where possible. Install
condensate drains from the fan coils to outdoors, and install new OSA
intake grilles through the wall to the new fan coil units. Install a
new chilled water pump, and a new hot water boiler, and a new hot water
pump. Install a second combustion air grille in the wall of the boiler
room. Flush the existing piping reused. Install one shot chemical
feeder on the hot water piping system. Turn window units over to the
owner. Install a new concrete pad outside of the exterior boiler room
stairs for new air cooled chiller. Rebalance entire facility air side,
grilles and units, and entire facility water side at coils. Add
backflow preventer to boiler make-up water. Install a new hot water
heating and ventilating unit to serve the basement storage room. Extend
new ductwork the length of the storage room at the ceiling line. Add
new fan coils with cooling to two rooms in the basement which are
presently heated and ventilated only. Install condensate pumps for
drainage removal. Insulate piping. Install wire, conduit, and circuit
breaker for chilled water pump, and install motor starter and non-fused
disconnect for chilled water pump. Install wire, conduit, and circuit
breaker for hot water pump, and motor starter and non-fused disconnect
for hot water pump. Install wire, conduit, and circuit breakers for
chiller, and install non-fused disconnect for chiller. Install
electrical connection for 20 fan coil units. The foregoing outline of
principal features does not in any way limit the responsibility of the
Contractor to perform all work and furnish all materials required by
the specifications and to perform other work items which may be
required or associated with this type of work. The estimated issue date
for this project is 07/06/95. A non-refundable fee of $25.00 will be
charged for each bid package requested by a bidder/offeror. Such fees
shall be in the form of check or postal money order payable to U.S.
Treasury and mailed to Directorate of Contracting, ATTN: Contract
Support Division, ATZR-QD, PO Box 33189, Fort Sill, OK. 73503-0189.
This project is unrestricted and ranges between $100,000 and
$250,000.(0173) Loren Data Corp. http://www.ld.com (SYN# 0152 19950623\Z-0002.SOL)